    0.1% Transformer Turns Ratio Test Kit , 500VA CT PT Analyzer


    Porable CT PT Test Equipment Analyzer MCVT405


    Main Features

    CT TestPT Test

    1) Excitation curve and parameters test

    2) Turns ratio test

    3) Ratio and phase error test

    4) Polarity mark check

    5) Winding resistance measurement

    6) Secondary burden measurement

    7) Error line curve test for protection CT

    8) Transient CT parameters test

    9) CT nameplate guess

    10) Saturation hysteresis loop curve measurement

    11) CT Residual Magnetism determination and demagnetization

    1) Turns ratio test

    2) Ratio error test

    3) Phase angle error test

    4) Polarity test

    5) Secondary burden test

    6) Winding resistance test


    • Accuracy limit value coefficient(ALF) • Instrument security factor(FS)

    Make evaluation for test results according to selected standards

    Make word report for test result

    Make word reports one time for multi-group test records on the PC

    Calculate ratio errors and phase angle errors at rated burden and working burden in one time test

    Compare excitation curves with saved excitation curves in the same window


    Applications

    • CT nameplate guess • CT parameters check in work burden • PT routine test

    • CT transient parameters analysis • CT ratio and phase error calibration


    Technical Index

    Test standardsIEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13
    Power supplyAC220V±10%, 50/60Hz±10%
    Voltage/Current output0.1~180V (AC) / 0.001~5A(RMS)
    Power output500VA
    Maximum knee voltage measurement45KV
    Current measurement
    Range0~10A (automatically change range in 0.1/0.4/2/10A)
    Error<±0.1%+0.01%FS
    Voltage measurement
    Range0~200V (automatically change range in 1V/10V/70V/200V)
    Error< ±0.1%+0.01%FS
    Turns ratio measurement & error
    Range1~35000
    Error1~5000 (error<0.05%) & 5000~35000 (error<0.1%)
    Phase measurement
    Error & Resolution±2min & 0.01min
    Winding resistance measurement
    Range0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm)
    Error< 0.2%RDG+0.02%FS
    Maximum resolution0.1mΩ
    Temperature measure
    Range & Error-50~100 Celsius degree & <3 Celsius degree

    CT Secondary burden

    Range0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)
    Error<0.2%RDG+0.02%FS
    Maximum resolution0.001ohm

    PT Secondary burden

    Range0~80kohm (automatically change range in 800ohm/8kohm/80kohm)
    Error<0.2%RDG+0.02%FS
    Maximum resolution0.1ohm

    PT ratio measurement & error

    Range1~35000
    Error1~10000 (error<0.1%) & 10000~35000 (error<0.2%)
    PT ratio error measurement
    ErrorTypical error <0.05%, Maximum Error<0.1%
    PT phase angle measurement
    maximum error< 3min
    Others
    Memory capacity>1000 groups test results
    Working conditiontemperature: -10℃~50℃; moist: ≤90%
    Size485mm×356mm×183mm
    Weight<15kg